No ac, found thermostat off upon arrival, set thermostat to call for ac and check indoor blower, blower does not come on, check wiring and found low voltage goin outside is not connected to indoor board, control board wiring is also not correct, condensation pump safety is not wired in, door switch is bypassed. Furnace was replaced this winter by home warranty company customer approved repairs after repairing wiring check operation ok ac, check supply and return air 74/52 unit is from 2005 uses Freon r22 would recommend replacement of air conditioning unit. Wiring repair on Low voltage side, noticed humidifier is not connected to furnace. It was never reattached to newer furnace. Customer will replace filter, did not check outdoor unit refrigerant pressures, there is Poison ivy around unit informed customer that he needs to take care of that, so we can check pressures and electrical, also provided an estimate to Reattach humidifier and onto furnace as well as drain for the humidifie