Performed ac tune up check electrical low and high ok flushed drown add tabs to trap, check blower cap and motor ok, check air split supply and return 20 degree split, noticed transition adapter is cracked and also two Big cracks on heat exchanger front plate, informed customer they need new heat exchanger and furnace should not be put in use, due to age and condition not worth installing new heat exchanger, would recommend new furnace, finished up ac tune check refrigerant pressures capacitor and contactor ok cycle unit ok emailed proposal to replace heat exchanger, we will follow up with customer about pricing on new furnace rebates and pricing