Found unit off upon arrival, start ac on both thermostats, found outdoor fan motor not running compressor over heating, hose off compressor and fan motor, both running but fan motor is running at 1.5 amps rated at 1.4 compressor takes seconds to start, and also found contactors coil sticking quotes for repair emailed quote Refrigerant pressures look ok 200/75