No cooling 3.5 Ton Trane AC system. High head pressures high subcooling. Found noticeable leaks on ubends of indoor coil. By the time homeowner had shut windows TD was 20F. 21 superheat; 14 subcooling 239/67. Problems are caused by a combination of leaking indoor coil and failed)clogged piston. Advised homeowner to use less restrictive filter and keep windows shut.