Completed AC tune up for 3 ton Lennox AC system. 16x25x1 filter ok Inspected condition of indoor and outdoor coils Measured temperature split and static pressure Checked drain and trap Inspected wiring, controls, electric motors and components: Outdoor dual run capacitor failed. Homeowner agreed to replace under warranty. Replaced today. There are no surge protection devices: Left email estimates. Monitored R410A refrigerant pressures and diagnostics: Good Verified integrity of compressor motor using megaohmeter. System is operating well at this time. The noise of condenser fan motor was caused by 2 slightly loose nuts that anchor motor from the top. Tightening these bolts resolved the sound. Office to contact homeowner regarding payment for warranty capacitor replacement.