Arrived to do a performance maintenance. Set both thermostats to heat and found that the zoning system would not open the basement dampers. Performed diagnostic and found that the zone control board can do either communicating thermostat control and traditional thermostat controls but not both at the same time. System is in need of an additional communicating thermostat. Replaced humidifier panel. Checked systems heat exchanger. System is operational upon departure.