6850 West 47th Tr
Mission, KS 66203

Local Reviews
for riverside, mo

Rated 4.9 out of 5 stars based on 7 customer reviews

Great customer service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service, very knowledgeable technicians.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service, good price, courteous men

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Very professional and courteous

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

She did a great job, explained what she was doing and why. Very pleasant and helpful. Great attitude!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Nick was very professional and courteous.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Mike was great

The service tech Mike was great. He did a great job a few weeks ago when he came and priced the system and a very clean and efficient job for the install.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for riverside, mo

Eli M.

Eli M. Job Checkin

Apon arrival I found that system noise was normal operation


Rylan H.

Rylan H. Job Checkin

Upon arrival found that thermostat was set for 78, indoor temperature was 73. Turned thermostat down to 68. System turned on as designed. System had a 19-21 degree split. System is operating within factory specifications at this time.


Michael S.

Michael S. Job Checkin

Performed a full cooling inspection. Checked all wires and safety switches. Cleaned outdoor unit. Unit is operating within factory specifications at this time.


Rigo  M.

Rigo M. Job Checkin

replaced both condenser fan motors and the main control board on the mini split that provides cooling for the IT room. After replacing the parts I turned the unit on tested it in cooling. Unit had a proper temp split and is currently operating properly at this time.


Rigo  M.

Rigo M. Job Checkin

arrived on site to diagnose mini split that is currently showing a alarm u8. The alarm code means “communication failure with outdoor fans”. After trouble shooting I found f5 fuse was blown I checked Mitsubishi tech support forms and it states “ replace control board and both condenser fans”. I was not able to get in contact with parts distributor to check availability of components. I will need to call and check In the morning.


Rigo  M.

Rigo M. Job Checkin

Arrived on site to the same issue with the same rtu. Unit was tripped on ignition lockout fault. I reset the unit and it began to operate properly, I checked the grounds for the entire unit. At this point I believe the control board is creating our intermittent issue. I can’t Guarantee it will fix the issue. I will be creating the quote in the morning once the part store opens.


Rigo  M.

Rigo M. Job Checkin

This quote is for replacing the inducer motor assembly on the rtu located on the south east corner of the building. Serial number is 0899G20467. Part is currently in stock, but can’t guarantee it is when quote approved. This quote includes all parts and labor. Inducer motor part # 50DK406815 1.5 hours of labor


Rigo  M.

Rigo M. Job Checkin

Upon arrival I spoke Robert the unit that I reset yesterday was not operating again. The unit was again locked out on “ ignition failure “ Which means there was no spark or no gas. I reset the unit and it fired up and operated fine with no issues. I turned the unit off and pulled the burners and cleaned them. I also pulled the flame sensor and cleaned it, turned the unit back and flame sensor was sensor 4.5 micro amps. I also checked the incoming gas pressure and it was 7. Inches of water column, and while firing it dropped to 6.7. The gas pressure out of the gas valve was 3.6 inches of water column. I reset the unit many times and I was never able to recreate the issue. The unit was running perfect for the 2 hours I was here on site.


Rigo  M.

Rigo M. Job Checkin

Arrived on site and spoke with Robert. He informed the 2 front rtu’s weren’t operating properly. I diagnosed both units and the first rtu had a failed inducer motor. The second rtu had a ignition fault, I reset the unit and it fired up and began to operate properly. I reset the unit multiple times trying to recreate the issue. I created a quote for the inducer motor replacement.


Doug A.

Doug A. Job Checkin

Checked to see if there was water pressure at wall, customer was unhappy stating that we’ve worked on there appliances before and didn’t know why we took the call. Did not charge service fee


John S.

John S. Job Checkin

Tested 3 backflow assemblies , all yielded passing results .


Matthew  R.

Matthew R. Job Checkin

Performed the preventive maintenance for the heating season. I checked the amp draw of the blower motor and inducer motor, I made sure that the blower wheel were in good working condition, I took readings of the capacitor to make sure that it was within the manufacturer's recommended tolerance, I looked over the heat exchanger to make sure there were no cracks or holes, I took a temperature split reading and I changed the filters.


Matthew  R.

Matthew R. Job Checkin

Replaced the failed ignition board on package unit. Checked to ensure system is operating at proper factory specifications. The unit is operating as designed.


Matthew  R.

Matthew R. Job Checkin

Upon arrival found unit locked out in ignition fault lockout. Found that ignition board has failed. Will get customer price to repair board.


Michael S.

Michael S. Job Checkin

Performed a full heating inspection. Checked all wires and safety switches. Performed a full heat exchanger inspection. Heat exchanger passed all test. Cleaned indoor unit. Unit is operating within factory specifications at this time.