6850 West 47th Tr
Mission, KS 66203
(913) 268-6822

Local Reviews
for eudora, ks

Rated 5.0 out of 5 stars based on 9 customer reviews

Excellent Service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service

Steve does a really great job

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Steve is Awesome to work with and very knowledgeable.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Steve is awesome to work with and is very knowledgeable

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Steve is an awesome guy to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Steve is great guy to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for eudora, ks

Rick B.

Rick B. Job Checkin

10-17-24 Got approval to make repairs on the Trane RTU Picked up parts Need to schedule to install. 10-14-24 During the heating check out, found the inducer motor and the ignition coil have failed. This quote is to install a new updated inducer motor assembly and ignition coil.


Steve R.

Steve R. Job Checkin

10-11-24 Performed heating check out I’m eight systems Note for me, I completed the tuneup however I need to do paperwork and write up a quote. I can do that after my next call.


Steve R.

Steve R. Job Checkin

8-30-24 Office AC systems #3 is not working and the thermostat is change your heat to cool by its self. We change the thermostat. The existing one was pretty old. Start up the 10 ton AC system ,when we checked the outdoor unit condenser found a the contactors were chattering they were getting 19 VAC The transformer may be the issue however this is a real long wiring run.I did get a voltage drop across both of my compressor time delays. I bypass the time delays for now and the time delay is in the in the thermostat 3 mins. Cycled system multiple times system is working at this time.Billy will keep an eye on it


Steve R.

Steve R. Job Checkin

6-11-24 Install new blower motor in the existing furnace for the plate room. Located above the bathrooms in the mezzanine area. System is working at this time.


Steve R.

Steve R. Job Checkin

6-5-24 Plate room hot AC is not working. The north system AC system is working, however I had to flush the condensate pump. The south system Bad blower motor in the furnace. I will pick up a new blower return and install it probably later this week. Have the motor on my truck


Steve R.

Steve R. Job Checkin

5-9-24 5 hrs Print press area Trane RTU I need to return tomorrow to continuous ticket. Pick uP some R22


Steve R.

Steve R. Job Checkin

4-12-24 Spring tuneup Hosed out all seven units on the ground did find some problems I need to return next week to complete check.


Steve R.

Steve R. Job Checkin

4-3-24 This JOB PO # 14511 The main office AC system is not working properly. The compressor was growling the last time I was up here. Trane condenser main office Model # 4TTA3060D4000CA Serial # 13362UF65F Today I found the AC condenser unit for the office disconnect was not pulling all the way in and also the two pole contactor was pitted real bad. Install new compressor contactor They supply me with some dielectric grease I was able to get the disconnect to work correctly however, in the future if we have issues we’re gonna have to replace them. Ran and cycle the AC system. Working at this time.


Steve R.

Steve R. Job Checkin

3-27-24 Install new 10 ton compressor on the 25 ton trane condenser unit. We were able to isolate the king valves at the condenser so we did not have to remove all the refrigerant back to the evaporator. After remove the refrigerant. Remove the existing bad compressor. Installed #1 circuit 10 ton compressor. The leak tested the isolated compressors,evacuated the two compressors to 500 microns. Then reinstalled the remote refrigerants. We ran and tested the unit. There is still bubbles in the cycle. System may have been low on refrigerant (R 410a) before we started the repair. I still need to install a new compressor contactor with auxiliary contacts The 2 crank case heaters are not working This was not part of the original quote however, I don’t want these compressors getting liquid back in them again. Note : I returned 2 core liquid line dryers that we didn’t use, that should come close to the same price as the heaters. 3-28-24 Return visit to install a compressor contactor an


TYLER M.

TYLER M. Job Checkin

3-27-24 Install new 10 ton compressor on the 25 ton trane condenser unit. We were able to isolate the king valves at the condenser so we did not have to remove all the refrigerant back to the evaporator. After remove the refrigerant. Remove the existing bad compressor. Installed #1 circuit 10 ton compressor. The leak tested the area, evacuated the two compressors to 500 microns. Then reinstalled the remote refrigerants. We ran and tested the unit. There is still bubbles in the cycle. System may have been low on refrigerant (R 410a) before we started the repair. I still need to install a new compressor contactor with auxiliary contacts two crank case heaters. This was not part of the original quote however, I don’t want these compressors getting liquid back in them again. I need to return tomorrow to complete this job. Also, I need to check out one of the AC units that was grinding over there. be in additional charge with the office system AC check out Quote to install ne


Steve R.

Steve R. Job Checkin

3-26-24 Compressor for tomorrow’s install


Steve R.

Steve R. Job Checkin

3-19-24 Filled out equipment survey as they could so we can give a proposal for an AC and fall tuneup They have a Filter service


Steve R.

Steve R. Job Checkin

3-18-24 Room AC, not working mouse got on top of the #1 10ton compressor contactor. Found the compressor was shorted to ground. We did replace #2 compressor back in August last year. There may be an issue that the compressor is getting liquid back to it. After we install this new compressor. We need to do some preventative circuits to prevent this from happening again. I will get a quote sent as soon as possible


Steve R.

Steve R. Job Checkin

11-28-23 East Chiller system for the printing press machine The east printing press machine is being removed from the premises. Chiller system today I’ve recovered 75 pounds of refrigerant R 22 to be disposed of. The condenser upon the roof, I disconnected it electrically and also cut the refrigerant lines to the unit so I could be removed from the roof. I also seal the refrigerant lines to the condenser. The chiller unit I cut the refrigerant lines and sealed the pipes going to the compressor. Disconnected the control wires going out to the condenser and also the main powers wires coming into the chili unit self.


Chris S.

Chris S. Job Checkin

9/22/23 Assisted Steve in an extensive cleaning. Binding area 20 ton AC system- Today Chris and I Opened up the air handler and cleaned the evaporator coil and the evaporator coil pan and drain. We used evaporator coil cleaner. and garden hose to clean. We did improve the static pressure drop across the coil. System is working at this time Evaporator coil was very dirty evaporator. The pan was full of dirt and muck.