6850 West 47th Tr
Mission, KS 66203
(913) 268-6822

Local Reviews
for eudora, ks

Rated 5.0 out of 5 stars based on 7 customer reviews

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Steve is Awesome to work with and very knowledgeable.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Steve is awesome to work with and is very knowledgeable

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Steve is an awesome guy to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Steve is great guy to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for eudora, ks

Steve R.

Steve R. Job Checkin

4-12-24 Spring tuneup Hosed out all seven units on the ground did find some problems I need to return next week to complete check.


Steve R.

Steve R. Job Checkin

4-3-24 This JOB PO # 14511 The main office AC system is not working properly. The compressor was growling the last time I was up here. Trane condenser main office Model # 4TTA3060D4000CA Serial # 13362UF65F Today I found the AC condenser unit for the office disconnect was not pulling all the way in and also the two pole contactor was pitted real bad. Install new compressor contactor They supply me with some dielectric grease I was able to get the disconnect to work correctly however, in the future if we have issues we’re gonna have to replace them. Ran and cycle the AC system. Working at this time.


Steve R.

Steve R. Job Checkin

3-27-24 Install new 10 ton compressor on the 25 ton trane condenser unit. We were able to isolate the king valves at the condenser so we did not have to remove all the refrigerant back to the evaporator. After remove the refrigerant. Remove the existing bad compressor. Installed #1 circuit 10 ton compressor. The leak tested the isolated compressors,evacuated the two compressors to 500 microns. Then reinstalled the remote refrigerants. We ran and tested the unit. There is still bubbles in the cycle. System may have been low on refrigerant (R 410a) before we started the repair. I still need to install a new compressor contactor with auxiliary contacts The 2 crank case heaters are not working This was not part of the original quote however, I don’t want these compressors getting liquid back in them again. Note : I returned 2 core liquid line dryers that we didn’t use, that should come close to the same price as the heaters. 3-28-24 Return visit to install a compressor contactor an


TYLER M.

TYLER M. Job Checkin

3-27-24 Install new 10 ton compressor on the 25 ton trane condenser unit. We were able to isolate the king valves at the condenser so we did not have to remove all the refrigerant back to the evaporator. After remove the refrigerant. Remove the existing bad compressor. Installed #1 circuit 10 ton compressor. The leak tested the area, evacuated the two compressors to 500 microns. Then reinstalled the remote refrigerants. We ran and tested the unit. There is still bubbles in the cycle. System may have been low on refrigerant (R 410a) before we started the repair. I still need to install a new compressor contactor with auxiliary contacts two crank case heaters. This was not part of the original quote however, I don’t want these compressors getting liquid back in them again. I need to return tomorrow to complete this job. Also, I need to check out one of the AC units that was grinding over there. be in additional charge with the office system AC check out Quote to install ne


Steve R.

Steve R. Job Checkin

3-26-24 Compressor for tomorrow’s install


Steve R.

Steve R. Job Checkin

3-19-24 Filled out equipment survey as they could so we can give a proposal for an AC and fall tuneup They have a Filter service


Steve R.

Steve R. Job Checkin

3-18-24 Room AC, not working mouse got on top of the #1 10ton compressor contactor. Found the compressor was shorted to ground. We did replace #2 compressor back in August last year. There may be an issue that the compressor is getting liquid back to it. After we install this new compressor. We need to do some preventative circuits to prevent this from happening again. I will get a quote sent as soon as possible


Steve R.

Steve R. Job Checkin

11-28-23 East Chiller system for the printing press machine The east printing press machine is being removed from the premises. Chiller system today I’ve recovered 75 pounds of refrigerant R 22 to be disposed of. The condenser upon the roof, I disconnected it electrically and also cut the refrigerant lines to the unit so I could be removed from the roof. I also seal the refrigerant lines to the condenser. The chiller unit I cut the refrigerant lines and sealed the pipes going to the compressor. Disconnected the control wires going out to the condenser and also the main powers wires coming into the chili unit self.


Chris S.

Chris S. Job Checkin

9/22/23 Assisted Steve in an extensive cleaning. Binding area 20 ton AC system- Today Chris and I Opened up the air handler and cleaned the evaporator coil and the evaporator coil pan and drain. We used evaporator coil cleaner. and garden hose to clean. We did improve the static pressure drop across the coil. System is working at this time Evaporator coil was very dirty evaporator. The pan was full of dirt and muck.


Steve R.

Steve R. Job Checkin

9-21-23 Picked up air compressor and evaporator coil cleaner at the shop


Steve R.

Steve R. Job Checkin

8-16-23 Yesterday we found the production area Trane rooftop unit was not cooling properly. This morning I checked the unit found #1 compressor was off on high head, pressure safety. Billy and I hosed out the condenser coil system is working at this time. After the compressor change out and contractor on the trane condenser unit yesterday. We found the compressor overload manual start unit was not fully engaging unless we forced it in. Billy was their when we found this. I picked up a new overload unit and install this morning.


Steve R.

Steve R. Job Checkin

7-27-23 Bonding area AC is not working Spoke to Billy on site Trane 25 ton Model# RAUJC254…………… Serial # C13K06009 Found the 2nd stage cooling 3 phase compressor contactor, has one leg closed, causing the compressor to single phase and trip off. Currently the compressor is damaged and when it does try to run, it blows the main fuses. I disabled this compressor so they can use for stage compressor for now however, Billy will turn the setting up on the thermostat not to stress that one compressor. We will send a quote to replace the compressor.


Steve R.

Steve R. Job Checkin

2-2-23thur Picked up variable speed control, Got on site, than got pulled off for another call. candle wood 2-3-23 fri Returned visit Today installs bathroom exhaust fan variable speed control. System is working at this time motor.


Steve R.

Steve R. Job Checkin

1-26-23 thu Back area Skyler‘s The printer that was removed was vented up to the roof. I had capped the exhaust on the roof the other day. Today they had some water dripping down. I got up on the roof and found that the Single wall flue piping was Condensating Inside the 2 elbows. Today I remove the 2 elbow so only 10” of single wall pipe is sticking up through the roof. I than capped that pipe and sealed the seam with roof tar. Billy is going to put insulation into the pipe from inside the building. They should prevent the pipe from condensing and dripping. material used today all supplied by the customer.


Steve R.

Steve R. Job Checkin

1-24-23 Tue 4.5 hrs Back area printing equipment exhaust, They remove the equipment. I installed a 14” cap on the roof to prevent rain from getting into the space. Billy also had me seal a couple potential leaks from the roof in that back room. Use their roof sealant. Bathroom exhaust motor was not running. Found the variable speed control was bad. I ordered a new variable speed control from interstate electric Should be in in a couple days