Service call that the Gas Furnace for the First Floor of the Home was not working. Upon arrival found furnace in the EO Error Code. Tested system and found Proper Pressure at the Front Door Pressure Switch. Pressure switch did not close on several attempts for the furnace to fire. The pressure switch began closing after several ignition retries. Exercised the Pressure Switch and the contacts were closing. Restarted system and cycled multiple times to ensure the Furnace was firing. Will follow up about replacement of the Pressure Switch.