Found wet switch was tripped with no water in pan. Wet switch tripped possibly beacause of very high humidity in the attic. Reset wet switch and system came right on. Did however re pipe drain beacause the drain that the installers originally pipped into is a very long run. Pipped into a secondary drain that goes straight out to the gutter and tested with water. A/c system is working fine again, can not prevent a wet switch from tripping from humidity in the air. System will take into the night now to cool down,