520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.


Job Locations
for berwyn, pa


Map of Berwyn PA
Dan S.

Dan S.


Job Checkin

No ac . found wet switch off and system down . when i checked high voltage / good . then i checked 24 / found 3 amp fuse blown for 24 volt transformer . checked wiring and found wires for wet switch shorted to ground . i fixed the wiring the replaced the fuse . aux pan had water in both front and back corners . i checked the coil pan to find systems cabinet had water in it from coil to blower . i checked coil pan for cracks / none . under the coil part of the system the pump up was in the middle of the coil were its only thin metal . the pump up was pushing the pan up right at the condensate outlet . the pump up had a rubber pad under it . i used band to hang coil part of system then moved pump ups that were at the coil side to the outside edge where there's thicker metal . i left straps on for extra support . i let the fan run for 20 mins to dry the water up in the unit. i then blew threw drain line to make sure nothing was clogged then tested out . system seemed to run fine and drain