Service call that the Heat Pump was not working. Upon arrival, found Thermostat set to 80 Degrees and the Indoor Temperature was 60 Degrees. Proceeded to the Air Handler to troubleshoot. Found Blower Motor was not operating. Turned Breaker off at the Air Handler to inspect Blower Motor Wiring. When we turned the Breaker back on the Blower began operating. The Relay in the Air Handler may have been stuck open causing the Blower not to run. Also found Air Filter excessively dirty and blocking Air Flow. Installed a 20x20x1 Air Filter. Tested Supply Temperature at 95 Degrees with a 65 Degree Return. Checked Refrigerant Pressures to ensure they were within range. The Air Handler is from 1982 and the Outdoor Unit is from 2001. The system is operating very inefficiently due to the very old age. System needs to be replaced due to poor condition. The office will be in contact to schedule an estimate for system replacement.