Service call that the Heat was not working. Upon arrival found home at 61 Degrees with system turned off. Turned heat on to 70 to test. Gas Furnace was not coming on and Indicator Light on Control Board was blank. Checked Voltages and found 120Volts incoming. Found Door Switch was broken which was keeping the system off. Bypassed door switch and put system in operation. Checked 16x25x1 Air Filter. Performed a combustion test and measured Air Temperatures. System has not had any maintenance performed since 2018. Would recommend replacing the Door Switch as this is a safety feature. If the blower door is opened the system will continue to run without the door switch. If opening door to change filter need to shut power off to furnace at the switch on the unit. Included an estimate for a new Door Switch and performing a Heating Tune Up on system.