Performed oil boiler check up, check electrical low and high ok replace nozzle .75x70b and RF-1 oil filter, clean and adjust electrodes good condition ok, clean heat exchanger and flue pipe ok performed smoke test and combustion test all numbers ok cycle boiler test ok test limit water pressure and temp ok noticed on primary control reading 900 ohms, informed customer might need to replace controller cad cell looks ok customer is aware situation