Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Performed ac check up, check electrical low and high ok replce filter 16x25x1 flushed drain ok, noticed has no ez trap and wet switch, recommended installing both safety’s, check outdoor unit, r22 seems to be ok, contactor is pitted, burnt contacts, and capacitor is reading 45x2.9 rated at 50x3 quoted fore repairs, Replace capacitor and contactor and also installed wet switch