Purge boiler system completely, all air is out of the system, check every baseboard and all getting hot, noticed outdoor reset sensor reading 54 currently temp is 51 measured outdoor temp with two different thermometers and both 51, adjust boiler curve soft ware to go from 130 min water temp to 150 minimum, boiler pressure need to be 20 psi for second floor to get heat, replaced feed valve old valve could not get up to 20 ps, for customer to get 100 heat of the baseboard, all baseboard fin needs cleaning, some of the them have no airflow passing through them, and not releasing water heat