Performed heat tune up, during visit customer informed heat would not come on during last weekend, found open igniter, replace igniter noticed control board always sending 120 volts to igniter during call for heat, that’s the cause why igniter went, quoted for new board and also upgraded to 120 volts igniter, customer ok with repair, installed new board and 120 igniter, clean sensor and check gas pressures ok combustion test cycle heater ok furnace running ok Now,