Removed two existing heat pump and air handlers. Installed new Amana heat pump and air handler. Installed new 15kw heat kit. Installed new supply plenum. Adapted to existing return box and drop. Sealed all ductwork. Ran new 7/8 lineset to new outdoor unit. Brazed pressure tested and evacuated to below 500 microns. Installed new single point entry kit and made all necessary high and low voltage connections. Adapted to existing 1.5 ton system ductwork and 10 in supply and return. Installed new condensate pump and tested. Installed new disconnect and whip. Installed new pad on stone and raised heat pump up on risers. Tested system in heating and cooling system working properly. Install went over with customer and work area cleaned.