Cleared condensation drain line and pump, upon arrival found blank thermostat, check all electrical low and high voltage , found open circuit on low voltage circuit, condensation ez trap float switch open, indicating drain blockage, provided an estimate to cleared drain line and test pump customer approved repairs, after clearing and cleaning drain line test condensation pump ok, flushed one gallon of water and add tabs to drain ok started ac unit, replaced customer supplied 423 filter, check supply and return temperature, 68/48 cycle unit ok.