Recently install HVAC UNIT not working, found unit locked out on high pressure fault, check low pressure and high pressure switch wiring, found low pressure switch wiring rubbing copper tubing from txv, tape wire using electrical tape and used cable tie to keep away from copper, check operation of entire system ran unit on cool regular heat and back up heat, check all settings and programming ok, check refrigerant pressures super heat and sub cooling ok delta split 18 F 72/54 performed quality assurance during visit overall installation looks good did not performed any changes or modifications regards installation. Set thermostat to cool 72 customer will set up schedule based on their needs.