Service call for that the Air Conditioner was not Cooling the Home and the Outdoor Unit Fan was not spinning. Arrived onsite and spoke with Homeowner about issue. Turned System to Cooling to test Operation. Found that the Compressor was running but the Condenser Fan Motor had failed and was seized. Shut power off to the system and removed the failed Fan Motor. Installed a new 208-230V 825 RPM Rescue Motor with a new Dual 50/7.5 Mfd Capacitor for the System. Made all wiring connections. Reassembled Condenser and put into operation. Measured Refrigerant Charge on system. Measured Amp Draw on the Fan Motor at 1.8 Amps, with the Motor rated for 1.9 Amps. Took Supply and Return Air Temperatures on the system. System is operating to standards at this time. Due to age and overall condition of the system, recommend begin planning/saving for replacement of the Gas Furnace/AC System.