Found disconnect was not plugged in from install and a/c breaker was turned off. Plugged in disconnect , turned on Breaker and tested a/c. Outdoor temp is 82 degrees and discharge air is 95 degrees. Pressure were 298/124 subcooling 11 and super heat is 18 very good. Delta t is 24 degrees. Also tightened some of the t stat connections at indoor board.