Checked no cooling complaint on second floor air conditioner, checked outdoor unit, found compressor off on internal overload, checked capacitor ok. Compressor reset. Started air conditioner, checked refrigerant charge, found low on charge. Also found oil in the base near the coil. Topped off charge, balanced by superheat. Checked operation ok.