Second opinion, per customer, they were told outdoor compressor was failing and probably would fail this summer, check indoor unit blowing pair, noticed attic unit and does not have water protection ez trap or wet switch, highly recommend installing water protection, filter ok check outdoor unit, looks like capacitor was recently change 50/5 check amp draw ok fan motor and compressor ok with in electrical range, check r22 pressures ok install d wet switch and ez trap for attic unit and also installed spp6 super boost for outdoor condenser unit test and cycle unit ok office will be calling to schedule maintenance visit under service plan