Reclaimed and removed old equipment. Installed new pad, disconnect, lineset, whip, and heat pump on heat pump feet. Brazed in outdoor unit and reconnected electrical. Installed new return box, return duct, and new air handler. Reconnected supply and return ducting. Installed heat kit. Ran new wire for air handler and tied into panel and unit. Installed new ez trap and condensate pump to break r wire. Brazed in air handler and pressure tested to 300. No leaks found. Evacuated down to 145 microns. Removed old oil tank fill and vent lines and closed holes. Removed old oil supply line. Installed new receptacle for condensate pump. Capped old chimny pipe. Ran vinyl into discharge line. Tested system and adjusted charge. Delta t 21 degrees. System working properly at time of install.