Performed 6 month inspections on two ac units, found wet switch tripped for attic unit, reset wet switch, clean filter for attic unit and for basement unit replace 15x25x1, both system were running at factory charge, added 1 1/2 lb 410 to attic and 1 lb for basement unit, check sub cooling and superheat ok target super heat for attic is 24 and current running at 21 super heat, for first floor unit target super heat is 19 and it is running at 20 both system are running at manufacturers specifications cycle both units ok supply temperature 52 return 75 for both units