Found incoming lp gas pressure at 12.3 w.c. With no draw on the tank. Gave gas furnace a call for heat and found on the manifold side only 2 w.c. With 11 incoming to the gas valve. Adjusted the low fire to 6 w.c. And high fire was at 10 w.c. Performed a combustion test. Regulators are functioning properly at time of service, gas valve just needed adjusted.