Brian B.

Brian B.


Job Checkin

Returned to install furnace control board, removed failed board, installed new furnace control board. Cycled air conditioner, found only fan getting a call. Replaced thermostat with supplied thermostat same thing happened, checked thermostat wires, found shorted thermostat wire to thermostat, found wire pinched between the drywall and a stud. Recommend installing a wireless thermostat. Relocated thermostat to basement for temporary cooling Need a wireless Honeywell thermostat. Returned to install wireless thermostat. Installed wireless module and wired. Connected thermostat to module. Cycled heat and cooling.