We replaced indoor coil yesterday, customer ran the ac unit and noticed water dripping from coil, found some frost/small layer of ice on indoor coil and around txv, outdoor unit cycling on and off, cleared coil and check refrigerant pressures 220/60 added 2 lbs of refrigerant to bring up pressures, ran unit for 20 minutes check super heat and sub cooling also supply and rerun air system is running ok, 6 degree sub cooling 16 super heat with supply temp 50 return air 68.