Found blown 30-5 MTD capacitor for 2Ton Trane XR 15 Heat pump. Cooled compressor with running water. Replaced capacitor. Tested system operation. Compressor amps 4.0; ok condenser fan amps .76; ok. 18F temp split (76F return- 58F supply. Filter ok. Cycled system once more. Left thermostat calling for cooling 70F. System is operating well at the time of this service.