Found condenser fan not operating. Determined need that a burnt relay in control board. Switched with control board from corridor unit 1 "CC1". Tested system operation. 18F temp rise. Hi pressure 353 Lo pressure 131. 6° subcool. Will order control board and schedule time to return to complete install of control board for unit CC1.