Found leaking evaporator coil Replace leaking coil. Recovered refrigerant charge from coil. Cut old coil free. Removed leaking coil. Set new coil. Pipe refrigerant lines, installed txv. Piped condensate drain. Pressure tested to 250 psi for 5 minutes. Evacuated system to 325 microns, held for 2 minutes. Opened refrigerant valves, started air conditioner, balanced refrigerant charge. Checked operation and temperature drop across coil. Emailed