Maintenance for 3 Ton mini split system that conditions the IT or server room. 25F temp rise with outdoor Air temp of 41F. Outdoor Voltage 212. Compressor amp draw OK. Filters were cleaned/ well maintained. Thermostat operation ok. System is working well at the time of this maintenance.