Installed new bolt on txv valve. Recovered all refrigerant. Brazed in new filter dryer. Removed old filter dryer that originally installed inside condenser unit. Pressure tested at 300 psi nitrogen. Soap checked fittings. No leaks. Pumped down system to 430 microns. Added 8 lbs 4 ozs of 410a. Started up a/c pressures were 185/98. Checked temperature split, temperature split was 19 degrees. System is working fine again at time of service.