Performed heating maintenance, checked air filter ok. Found electric heated cycle on limit and no blower. Found thermostat is not calling for electric heat, found electric heater relay stuck closed. Replaced electric heat relay. Tested electric back up heaters. Started heat pump, measured btu output. Tested defrost cycle. Checked operation and temperature rise across coil. Serviced humidifier and replaced water panels. Started and checked operation. Set humidistat to 35% rh.