Barry P.

Barry P.


Job Checkin

No Cooling. Outdoor 45-05 capacitor reading 0 between HERM and common and 1.2 between FAN and common. Mrs Menta approved repair. Replaced capacitor. Ran system in cooling. 17F temp split. System is operating well at the time of this service.