After talking to homeowner, peco was out and shut off power to boiler and shut off valve outside the furnace beacause what they found was after the burners were done heating and the gas valve was supposed to close it was leaking gas through out the burners. Soap checked gas fittings going into boiler at drip leg and found no other leaks. Turned gas on to boiler and did not see it bleeding through at the time, but recommended that if there is and bleeding through of the gas to have the valve replaced. Replaced gas valve and checked manifold pressure at 3.3w.c.. soap checked for leaks. Cycled gas valve several times, is functioning correctly. Performed combustion test. Gas boiler is working at time of service