Checked no heat, found roll out switch open. Reset roll out, started furnace, checked fuel pressures, got 11.73â€. Performed combustion test, found furnace making over 2500 ppm co. Backed fuel manifold pressure back to 6†made no difference. I can see the right chamber with impinged flame. Shut furnace down un shaft to run. Sales appointment is set up