7-27-23 Bonding area AC is not working Spoke to Billy on site Trane 25 ton Model# RAUJC254…………… Serial # C13K06009 Found the 2nd stage cooling 3 phase compressor contactor, has one leg closed, causing the compressor to single phase and trip off. Currently the compressor is damaged and when it does try to run, it blows the main fuses. I disabled this compressor so they can use for stage compressor for now however, Billy will turn the setting up on the thermostat not to stress that one compressor. We will send a quote to replace the compressor.