3/28/24 - Completed a full cooling maintenance on one York RTU. The filter was changed and all parts were checked. Unit is a little on the older side, but everything seemed to be running fine. Overall, there were no issues found at this time, and it should continue to run well.
During this visit I performed a fall heating maintenance on the rooftop unit that serves the office and waiting room. The unit was checked for both electrical and mechanical functions. All heating checks are in range today. In addition to this the condensation drain was removed and cleaned, the insulation for the blower compartment door was reattached on the corners with adhesive and the filter was replaced. Thank you, Jon Tech notes: s/n N1D1909945, tr 41, odt 67, fs 3.3, ind 0.51, Indoor blower 3.34 (ECM), bearings good. Heat exchangers good (no CO)