Rtu #2 was not running when I arrived. Found that the system had trip out on high pressure on the cooling side. This is due to lack of maintenance and the filters are completely clogged and has not been changed since January of 2024. Also that the condenser is also completely clogged with dirt and cotton wood. This unit needs to breathe. I recommend changing the 16x20x2 (4) fliters and washing/ deep clean the condenser out to allow proper air flow for the unit. Jackie is waiting on a ok to do so and can’t get ahold of them at this time. She will call back when she gets approval to do so