No drain line was connected to the humidifier during install. This left water all over the crawl space and ductwork. I ran drain line and tested water to make sure there were no other issues. I notifu]ied my managers for them to handle situation from here.
Completed furnace maintenance and inspection. I tested all components and amp draws. I made sure humidifier worked and that the filter was clean. Customer mentioned compressor sounded loud so I checked running amps, voltage, and start amps. Compressor was over amping at start so I added a hard start kit which dropped the start amps down to 64 amps.
Water filtration system installed at a residential home. Upon completion the system was tested to confirm it effectively removes impurities, providing clean, safe drinking water.
Found system had extremely high static pressure and bad airflow with ducts full of water. Complete ductwork system was set up improperly and failing. Customer agreed to do 5 star complete duct restoration this Friday.