Arrived for ac check today. Started at furnace and checked static pressure, it is running over the max. Blower wheel is building up with dust. Motor amps are good. There is a 23 degree temp split. At the condensing unit all pressures and charge look good. All electrical components are running within specs. I rinsed coil clean. System is running upon departure. Thanks for choosing LBA.