A9 Shipping area motor not functioning Scissor lift on-site 5 unit heaters 2 of 3 indoor rtus not functioning Gas valve unit #7 wr, 36C01A type 284, microprocessor fenwal, #35-725911-117 Unit #8 gas valve (same as above), microprocessor fenwal #35-725911-117 Unit #10 gas valve open windings. Voltage to gas valve 120v. Unit heater #2 Fan motor needed. Motor info: Mc Millan electric company, m/n A0828B2842, E62788, E62815, E62862, 120V 1ph, 60hz, 5.8amp. **fan blades 18” x 4. Factory fan blade p/n *grainger Century 4MB26. $216.03 in stock Kansas City. 3sp 1075 rpm, 1/3rd hp *Grainger Ignition board //fenwall board discontinued. Solaronics: 826PA5 needs to be ordered. $564.90 *grainger gas valve // discontinued 4E126 Robertshaw $270.75 in stock at distribution center. All infrared heaters are solar on is brand (*)*((&)&(&)&&((&)&)(&)&)$(&)&)&(&)&))*(*(*(**(*(**((*((**(( Hanging infrared heater #7 Fenwal microprocessor # 35-725911-117 (line voltage control). Voltage enters