Multiple issues going on here the reason the outdoor stopped working is due to a fan not operating because of this the condenser is turning on by itself. Checked the capacitor annd its good. contactor is an extremely rough shape and the condenser has definitely seen better days. It’s overfilled with our 22 and because of this the liquid line is actually sucking in pressure which is sucking in oxygen into the condenser. This is the part of the reason that the condenser sounds terrible and is operating terrible. at this point it’s kind of of irreversible without evacuating all the R 22 and looking for the leak. But with our 22 not being used anymore, this would be an extremely expensive route. The system is 24 years old and my professional opinion is it definitely need to get replaced. You can keep dumping money on parts to fix this and that but in the long run, I don’t think you’re gonna save money. After checking the furnace, the AC coil is extremely rusted and if I had to guess what t