🔧 Second Opinion System Evaluation Summary Dispatched to provide a second opinion after another company advised that the HVAC systems were undersized for the home. A full system evaluation was completed, including a manual load calculation based on the square footage, layout, and construction of the home. The load calculation results determined the following requirements: • Cooling demand: 42,000 BTUs • Heating demand: 71,000 BTUs The home is currently equipped with two heat pump systems, each consisting of: • 30,000 BTU heat pump • 15 kW electric heat strips per system Each 15 kW heat strip produces approximately 51,000 BTUs of heat. When combining both systems, the home has: • 60,000 BTUs of heat pump capacity • 102,000 BTUs of electric heating capacity from heat strips alone This confirms that the home has more than enough heating and cooling capacity and is not undersized, as previously stated. ⸻ 🔍 Findings & Recommendations The primary issues identified are not rel