Arrived on site to perform the leak test, pressurized with 400 psi of nitrogen and found that the outlet fitting of the expansion valve onto the coil was leaking. Tightened up and confirmed that there was no more signs of bubbles and allowed the system to hold pressure and confirm that it is no longer leaking. Evacuated the system and charged up with R410A.