Repaired lineset leak. Performed pressure test and evacuation. Brought system down to 675 microns. System would not hold negative pressure. Recharge with 10 pounds. System cooling but not well. Only 14 degrees temperature drop. 82/68. High suction pressure. Low head pressure. 150/300. Low superheat low sub cooling . Indication of a restriction or failing compressors.