Arrived for ac check today. Started at furnace and blower wheel is clean. Motor amps are within range. You’ve been changing filters. There is a 23 degree temp split. At the outdoor unit I cleaned the coil. Pressures and charge looked good. Compressor and fans amps are within range. Capacitor is good. System is running upon departure. Thanks for choosing LBA.