8-16-25. Spoke to Patrick earlier the issue is the showroom in the used. Car building is extremely hot. Upon arrival spoke to the gentleman at the desk, forgot his name. He did say they’ve had some power outages Showroom is extremely hot, thermostat was reading 92° I got up on the roof located to York RTU. There was only one rooftop unit the serial #N1E0842316 I found the board leaking the code ignition control failure. I’m pretty sure they were not running heat, but it may have locked out in this position when the power went out or had a power surge. I reset the unit electrically from the service disconnect. Let it sit for a couple minutes. Re-energize the unit. In a couple minutes. The unit came back on and is running in AC mode with both compressors. Not showing any fall codes unit run for about 15 minutes. While I was waiting, I went ahead and glued the 1 inch PVC P-trap fittings together. The trap is there, but nothing is glued. After a little bit, the system is running. I’ve